HomeFire & RefugeESP 2 Zone Fire Panel |
|
ESP 2 Zone Fire Panel £125.40
![]() 2 Zone ABS Conventional Fire Panel Technical Specification:Inputs:Max Detectors Per Zone: 30 Thresholds for Zone Conditions: 0 - 2 mA (Fault condition) 2 - 6 mA (Normal condition) 6 - 110 mA (Fire condition) 110 mA - Short (Fault condition) Power: Mains Fail Consumption : 50mA Mains Supply: 230 VAC ± 10% Standby Supply: 1 x 7ah 12V S.L.A. Battery Power Availability: 0.7 amps Outputs: Sounder 1: 24V (max 300mA fused) Sounder 2: 24V (max 300mA fused) Fault/Fire Relay: Volt free 500mA @ 24V (max load) Auxiliary Output: 24VDC (300mA fused) Environment: Working Temperature: 0 to 40ºC Storage Temperature: -20 to 60ºC Humidity: 0 - 95% Dimensions MAG2P: 340 x 290 x 100mm Dimensions MAG2: 200 x 290 x 80mm Weight: MAG2P - 2.1Kg MAG2 - 2.7Kg